Machine delivered with a Control Box (Option)
DANGER
Live wires.
Risk of electrical shock.
- Electrical installation work must only be executed by qualified personnel.
- Make sure that the power supply for the motor is compatible with the data on the nameplate of the control box.
- If the machine is equipped with a power connector, install a residual current protective device to protect persons in case of a defective insulation.
- Busch recommends installing a type B residual protective device suitable for the electrical installation.
- If the control box is not equipped with a lockable disconnect switch, provide it on the power line so that the machine is completely secured during maintenance tasks.
- Provide an overload protection according to EN 60204-1.
- Connect the protective earth conductor.
- Electrically connect the control box.
NOTICE
Incorrect connection.
Risk of damage to the control box and motor!
- The wiring diagrams given below are typical. Check the inside of the control box for connection instructions/diagrams.