Machine delivered without Control Box or Variable Speed Drive (VSD)
DANGER
Live wires.
Risk of electrical shock.
- Electrical installation work must only be executed by qualified personnel.
 
- Make sure that the power supply for the motor is compatible with the data on the nameplate of the motor.
 - If the machine is equipped with a power connector, install a residual current protective device to protect persons in case of a defective insulation.
 - Busch recommends installing a type B residual protective device suitable for the electrical installation.
 - Provide a lockable disconnect switch or an emergency stop switch on the power line so that the machine is completely secured in case of an emergency situation.
 - Provide a lockable disconnect switch on the power line so that the machine is completely secured during maintenance tasks.
 - Provide an overload protection according to EN 60204-1 for the motor.
 - Busch recommends installing a D-curve circuit breaker.
 - Connect the protective earth conductor.
 - Electrically connect the motor.
 
NOTICEIncorrect connection.
Risk of damage to the motor!
- The wiring diagrams given below are typical. Check the inside of the terminal box for motor connection instructions/diagrams.
 